Back to Search Start Over

Experimental study of a bilinear control for a GSHP integrated air-conditioning system.

Authors :
Gao, Jiajia
Huang, Gongsheng
Xu, Xinhua
Source :
Energy & Buildings. Dec2016, Vol. 133, p104-110. 7p.
Publication Year :
2016

Abstract

This paper presents an experimental study on a bilinear temperature control of a ground source heat pump (GSHP) integrated variable air volume (VAV) air-conditioning system, which may experience significant variations in the supply air temperature due to the frequent on/off switch of the ground source heat pump and the low thermal capacity at the air side. The bilinear control was realized in a building automation system (BAS) and applied to a test rig. The experimental results show that with an online estimation of the cooling load the bilinear control was able to maintain the space temperature at its set-point well and the control performance was superior to that of a conventional PI control. Therefore, the bilinear control has the potential to be used in GSHP integrated air-conditioning systems to improve the robustness and accuracy of the space temperature control. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
03787788
Volume :
133
Database :
Academic Search Index
Journal :
Energy & Buildings
Publication Type :
Academic Journal
Accession number :
119582135
Full Text :
https://doi.org/10.1016/j.enbuild.2016.09.021