Back to Search Start Over

Secondary Sodium Fire Measures in JSFR.

Authors :
Yoshitaka Chikazawa
Atsushi Katoh
Tomohiko Yamamoto
Shigenobu Kubo
Shuji Ohno
Mikinori Iwasaki
Hiroyuki Hara
Yoshio Shimakawa
Hiroshi Sakaba
Source :
Nuclear Technology. Oct2016, Vol. 196 Issue 1, p61-73. 13p.
Publication Year :
2016

Abstract

The Japan Sodium-cooled Fast Reactor (JSFR) adopts a double boundary for all sodium components. In this paper, design measures are investigated against a secondary sodium fire inside the reactor building, which might be assumed as design extension conditions. Candidate sodium fire measures for the secondary sodium systems compared in terms of safety are the sodium drain, nitrogen injection, pressure release valve, catch pan, and drain system for leaked sodium. Various sodium fires in the steam generator room have been analyzed by the SPHINCS code to evaluate the performance of the candidate sodium fire measures. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
00295450
Volume :
196
Issue :
1
Database :
Academic Search Index
Journal :
Nuclear Technology
Publication Type :
Academic Journal
Accession number :
118533285
Full Text :
https://doi.org/10.13182/NT15-131