Evaluation of utility transformers' lifespan with different levels of grid-connected photovoltaic systems penetration.

Authors :
Manito, Alex R.A.
Pinto, Aimé
Zilles, Roberto
Source :
Renewable Energy: An International Journal. Oct2016 Part A, Vol. 96, p700-714. 15p.
Publication Year :
2016

Abstract

This paper evaluates how grid-connected photovoltaic penetration level would affect utility transformers by changing the thermal stress to which these components are subjected. The analyses carried out used typical commercial and residential load curves, and considered variations in photovoltaic penetration, load and weather data. In addition, a loss analysis was carried out for a typical 100 kVA transformer in each of the simulated situations. According to the calculations, an extension in the lifespan of the transformer could be achieved depending on the matching between PV generation and demand, which may represent financial gains. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
09601481
Volume :
96
Database :
Academic Search Index
Journal :
Renewable Energy: An International Journal
Publication Type :
Academic Journal
Accession number :
115920651
Full Text :
https://doi.org/10.1016/j.renene.2016.05.031