A systematic parametric study and feasibility assessment of solar-assisted single-effect, double-effect, and triple-effect absorption chillers for heating and cooling applications.

Authors :
Shirazi, Ali
Taylor, Robert A.
White, Stephen D.
Morrison, Graham L.
Source :
Energy Conversion & Management. Apr2016, Vol. 114, p258-277. 20p.
Publication Year :
2016

Abstract

The present work investigates the feasibility of solar heating and cooling (SHC) absorption systems based on combining three types of LiBr–H 2 O absorption chillers (single-, double-, and triple-effect) with common solar thermal collectors available on the market. A single-effect chiller is coupled with evacuated tube collectors (ETCs) – SHC1. A double-effect chiller is integrated with parabolic trough collectors (PTCs), linear Fresnel micro-concentrating collectors (MCTs) and evacuated flat plate collectors (EFPCs) respectively – SHC2, SHC3, and SHC4. PTCs are employed to provide high-temperature heat to a triple-effect absorption chiller (SHC5). Although triple-effect chillers have been around for a while, this paper represents the first system-level analysis of these chillers coupled with high-temperature solar concentrating collectors for air-conditioning applications. A simulation model for each configuration is developed in a transient system simulation environment (TRNSYS 17). Furthermore, a unique, comprehensive perspective is given by investigating the impact of characteristic solar beam radiation to global radiation ratios on the techno-economic performance of the proposed SHC plants for a wide variety of climatic regions worldwide. The results of parametric study suggest that a storage volume of around 70 L/m 2 is a good choice for SHC1, while 40–50 L/m 2 storage capacity is sufficient for the other configurations (SHC2 to SHC5). The simulation results reveal that when the fraction of direct normal irradiance (DNI) is less than 50%, SHC2, SHC3, and SHC5 require larger collector area compared to SHC1, showing there is no advantage in using concentrating collector powered multi-effect chillers over solar single-effect chillers in climates with low DNI level. However, in climates with DNI fractions above 60%, the smallest solar field is achieved by SHC5, followed by SHC2. SHC4, which benefits from both relatively high COP of double-effect chiller and the diffuse component in the solar field, results in the most reasonable trade-off between energetic and economic performance of the system in a wide range of climatic conditions. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
01968904
Volume :
114
Database :
Academic Search Index
Journal :
Energy Conversion & Management
Publication Type :
Academic Journal
Accession number :
113428485
Full Text :
https://doi.org/10.1016/j.enconman.2016.01.070