Back to Search
Start Over
Retrofitting of R404a commercial refrigeration systems using R410a and R407f refrigerants.
- Source :
-
International Journal of Refrigeration . Jul2015, Vol. 55, p142-152. 11p. - Publication Year :
- 2015
-
Abstract
- This paper presents an experimental analysis about the retrofitting of two commercial stationary refrigeration systems marketed by an Italian leading company. Such systems operate both at medium temperature (MT), i.e. [−5; 10]°C, and low temperature (LT), i.e. [−25; −15]°C, and they are originally designed to work with hydrofluorocarbon (HFC) R404a, known as a high global warming potential (GWP) fluid (GWP = 3922). The goal is to investigate the performances of HFC R410a (GWP = 2088) and R407f (GWP = 1825), chosen as effective alternatives to HFC R404a. Such fluids are compatible with the refrigeration systems, non-flammable and easy-available. Furthermore, they meet the European Union (EU) restrictions in force in the next future, so that they are suitable to start the transition toward efficient and eco-friendly refrigeration systems. The experimental campaign shows the feasibility of adopting R407f and R410a for the MT refrigeration system and R407f fluid for the system operating at LT. [ABSTRACT FROM AUTHOR]
Details
- Language :
- English
- ISSN :
- 01407007
- Volume :
- 55
- Database :
- Academic Search Index
- Journal :
- International Journal of Refrigeration
- Publication Type :
- Academic Journal
- Accession number :
- 103408126
- Full Text :
- https://doi.org/10.1016/j.ijrefrig.2015.02.015