Back to Search
Start Over
Seismic retrofitting of an HV circuit breaker using base isolation with wire ropes. Part 1: Preliminary tests and analyses.
- Source :
-
Engineering Structures . Sep2015, Vol. 98, p251-262. 12p. - Publication Year :
- 2015
-
Abstract
- This paper briefly describes the design and characterisation of a base isolation system that protects HV ceramic circuit breakers during seismic events. This qualifies them to the European standard CEI EN 62271-207. The solution is based on an innovative application of wire rope isolators. Preliminary numerical analyses and tests were performed on a typical HV circuit breaker and demonstrated the effectiveness of the proposed isolation system in reducing seismic demand. The results were also validated using a shaking table, which is described in an accompanying paper. The on-site installation of this system in several Italian substations has finally proved simple enough to upgrade the equipment for seismic protection. [ABSTRACT FROM AUTHOR]