Back to Search Start Over

Seismic retrofitting of an HV circuit breaker using base isolation with wire ropes. Part 1: Preliminary tests and analyses.

Authors :
Alessandri, S.
Giannini, R.
Paolacci, F.
Malena, M.
Source :
Engineering Structures. Sep2015, Vol. 98, p251-262. 12p.
Publication Year :
2015

Abstract

This paper briefly describes the design and characterisation of a base isolation system that protects HV ceramic circuit breakers during seismic events. This qualifies them to the European standard CEI EN 62271-207. The solution is based on an innovative application of wire rope isolators. Preliminary numerical analyses and tests were performed on a typical HV circuit breaker and demonstrated the effectiveness of the proposed isolation system in reducing seismic demand. The results were also validated using a shaking table, which is described in an accompanying paper. The on-site installation of this system in several Italian substations has finally proved simple enough to upgrade the equipment for seismic protection. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
01410296
Volume :
98
Database :
Academic Search Index
Journal :
Engineering Structures
Publication Type :
Academic Journal
Accession number :
102880118
Full Text :
https://doi.org/10.1016/j.engstruct.2015.03.032