Back to Search Start Over

Thermal-Electric Rating Method for Mass-Impregnated Paper-Insulated HVDC Cable Circuits.

Authors :
Huang, Z. Y.
Pilgrim, J. A.
Lewin, P. L.
Swingler, S. G.
Tzemis, G.
Source :
IEEE Transactions on Power Delivery. Feb2015, Vol. 30 Issue 1, p437-444. 8p.
Publication Year :
2015

Abstract

Compared to conventional ac cables, the current rating of HVDC cable circuits is more complicated because the permissible current is not only limited by the operating temperature, but also by the electrical stress within the insulation. Therefore the IEC60287 current rating standard is considered insufficient for some HVDC applications because it fails to include the stress limitation. This paper presents an analytical methodology to calculate an electrical stress-limited rating for HVDC cables, which considers the maximum dielectric stress as the current limiting factor. This paper represents the first part of a project which has comprehensively reviewed cable rating calculations for mass impregnated HVDC cable systems. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
08858977
Volume :
30
Issue :
1
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
100608531
Full Text :
https://doi.org/10.1109/TPWRD.2014.2359772