1. Research on DC Bias Saturation Characteristics of Transformer Combining CEEMD and FuzzyEn Method.
- Author
-
Xingmou Liu, Rui Lu, Ning Yang, Yao Xiao, and Jadoon, Ammad
- Abstract
To address the challenge of accurately determining the saturation state induced by transformer DC bias, we propose a combined method for analyzing the DC bias of the transformer using vibration signals. This method employs the complementary ensemble empirical mode decomposition (CEEMD) to preprocess the vibration signals and fuzzy entropy (FuzzyEn) to assess the degree of DC bias. The optimal measurement point of the transformer is determined through transformer mechanical analysis. Subsequently, a vibration test. experimental platform is established to capture vibration signals at five distinct points on the transformer shell and core. These signals are then subjected to CEEMD for reconstruction, enabling the determination of the degree of DC bias. This assessment is based on fuzzy entropy values and difference curve analysis. The results demonstrate that the FuzzyEn value, serving as an indicator of the iron core's saturation due to DC bias, effectively detects the level of DC bias. Upon reaching its maximum value, the FuzzyEn of the vibration signal signifies the core's entry into the saturation zone. Specifically, the maximum FuzzyEn value is approximately 1.5 A on both sides of the core, about 1 A on the left and right sides of the shell, and 2 A in the middle of the shell. These findings confirm the efficacy of the combined CEEMD and FuzzyEn method. [ABSTRACT FROM AUTHOR]
- Published
- 2024