1. A Practical Solution for Locating the Source of Voltage Dips in HV/MV Interconnected Grids
- Author
-
Paolo Castello, Carlo Muscas, Paolo Attilio Pegoraro, Sara Sulis, Johan Rens, and Jacobus Van Zyl
- Subjects
Voltage dips ,power quality meter ,field data platform ,time accuracy ,synchronization ,Distribution or transmission of electric power ,TK3001-3521 ,Production of electric energy or power. Powerplants. Central stations ,TK1001-1841 - Abstract
Monitoring the technical performance of a power system is significantly enhanced when distributed instrumentation produces coherent field data, i.e., synchronized by GPS timestamping. In this paper a practical methodology is presented to improve the localization of the source of a voltage dip on power grids. The proposed solution makes use of synchronized dip data provided by power quality meters. Field data reporting events occurred in an HV/MV interconnected system in South Africa are used to validate the results obtained by the improved method and compare with results of two alternative methods.
- Published
- 2023
- Full Text
- View/download PDF