101. Improving DFIG performance under fault scenarios through evolutionary reinforcement learning based control
- Author
-
Wei Gao, Rui Fan, Renke Huang, Qiuhua Huang, Yan Du, Wei Qiao, Shaobu Wang, and David Wenzhong Gao
- Subjects
Distribution or transmission of electric power ,TK3001-3521 ,Production of electric energy or power. Powerplants. Central stations ,TK1001-1841 - Abstract
Abstract The doubly fed induction generator (DFIG) usually experiences high rotor current and DC capacitor link voltage spikes during system fault events. In this paper, a novel data‐driven approach is proposed to enhance DFIG performance under fault scenarios. An advanced reinforcement learning algorithm called guided surrogate‐gradient‐based evolution strategy (GSES) is used to control the DFIG power and capacitor DC‐link voltage by adjusting the optimal reference signals. This controller is able to prevent the DFIG rotor from over‐current risk and maintain grid‐connected operation. The proposed GSES‐based control algorithm was evaluated through simulations on a 3.6‐MW DFIG in the PSCAD/EMTDC software. Results have validated the effectiveness of the proposed GSES‐based control algorithm in improving DFIG performance under various fault scenarios.
- Published
- 2022
- Full Text