1. Fire tower tests of stair pressurization systems with mechanical venting of the fire floor
- Author
-
Tamura, G. T.
- Subjects
régulateur de fumée ,escalier ,Incendie ,pressurization ,smoke controls ,stairs ,Indoor air ,high rise buildings ,construction élevée ,Fire ,pressurisation ,Air intérieur - Abstract
Stairshaft pressurization systems under various schedules of stair door operation, nonfire/fire conditions, and the fire floor vented with an exhaust fan were investigated in a 10-storey experimental fire tower. The four stairshaft pressurization systems that were tested had overpressure relief features of exit door relief, barometric damper relief, feedback control with fan bypass, and feedback control with variable-speed fan. Tests have indicated that with any one of the stair pressurization systems on and with mechanical venting of the fire floor, the stairshaft was kept smoke free with four stair doors open., Reprinted from: ASHRAE Transactions 1990, v. 96, pt. 2, p. 384-392, ISSN: 0001-2505, Presented at the 1990 ASHRAE Annual Meeting, St. Louis, MO, USA, June 9-13, 1990
- Published
- 1990