1. Analysis on Protection Coordination of OCRs Using Voltage Components for the Application of SFCL in a Power Distribution System with DG.
- Author
-
Lim, Sung-Hun and Park, Min-Ki
- Subjects
- *
POWER distribution networks , *SUPERCONDUCTING fault current limiters , *POWER system simulation , *FAULT currents , *PROTECTIVE relays , *ELECTRIC relays , *OVERCURRENT protection - Abstract
As the importance of renewable energy increases, the capacity of dispersed generations (DGs) has increased worldwide. However, the connection of DGs in the power distribution system can cause the fault current to increase as well as malfunction of the overcurrent relay (OCR) due to the reverse directional fault current. As the countermeasure to limit the fault current in the power distribution system with DG, though the superconducting fault current limiter (SFCL) is reported to be more effective, the research on the protection algorithm of the protective relay considering the application of SFCL is preferentially required. In this paper, the correction method of the OCR using voltage components for application of SFCL in a power distribution system with DG was suggested. To verify the effectiveness of the suggested method, the fault simulation for the power distribution system with DG including the OCR and the SFCL was performed. By applying the proposed correction method in the OCR, the protection coordination of OCRs for the application of SFCL in power distribution system with DG was confirmed to be improved through the suppression of the malfunction of the OCR. [ABSTRACT FROM AUTHOR]
- Published
- 2021
- Full Text
- View/download PDF