1. Operation and control of coupled nonequilibrium disk MHD generator and inverter system under power line fault condition.
- Author
-
Inui, Yoshitaka, Ishikawa, Motoo, and Hayashida, Hiroshi
- Subjects
- *
MAGNETOHYDRODYNAMIC generators , *NONEQUILIBRIUM plasmas , *ALTERNATING current generators , *ELECTRIC power production , *MAGNETOHYDRODYNAMIC electric power generation , *ELECTRICAL engineering - Abstract
Numerical simulations of detailed time-dependent behavior are performed on a simulation model in which a coupled system of nonequilibrium disk MHD generator and line-commutated inverter is connected to an infinite bus through the transmission line, showing that continuous operation of the system is usually possible even when a power line fault occurs near the system. Then, time-dependent swing simulations are carried out on another simulation model in which the MHD/inverter system and a synchronous generator are connected in parallel to an infinite bus through the common transmission line, revealing that the rotor angle swing of the synchronous generator caused by the power line fault can be effectively suppressed by the fast output power control of the MHD/inverter system. © 1999 Scripta Technica, Electr Eng Jpn, 127(3): 13–24, 1999 [ABSTRACT FROM AUTHOR]
- Published
- 1999
- Full Text