1. Discharge characteristics of 5 m long air gap under foggy conditions with lightning shielding of transmission line
- Author
-
T. Shindo, S. Taniguchi, S. Okabe, and Tsuguhiro Takahashi
- Subjects
Engineering ,business.industry ,Acoustics ,Electrical engineering ,Conductor ,Lightning strike ,Electric power transmission ,Transmission line ,Electromagnetic shielding ,Electrical and Electronic Engineering ,Air gap (plumbing) ,business ,Electrical conductor ,DC bias - Abstract
The electric geometry model suggested by Armstrong and Whitehead was used to calculate the performance of lightning-shielded transmission lines. However, since the ultra high voltage (UHV) designed transmission lines were brought into 500 kV operation, it has become evident that their actual performance is different from the calculated predictions in terms of their actual faults, lightning observation results, etc. It is thought that the UHV designed transmission lines are subjected to foggy or rainy conditions when lightning strikes, because they often pass through mountainous areas at higher altitudes. However, according to the electric geometry model, the striking distance is determined by the lightning-stroke current value only, and the model does not consider the environment of discharge path for the relevant lightning strokes. These considerations suggest that foggy conditions may affect transmission line lightning shielding performance. In this study, discharge tests were conducted using a scaled-down transmission line with a 5 m air gap. The discharge point to the simulated conductor was analyzed in both dry and foggy conditions. Tests were also conducted with a DC bias applied to the simulated power lines, to take the operating voltage of the lines into consideration. These experiments have shown that the effect of fog on the discharge ratio to the conductors is negligible.
- Published
- 2008
- Full Text
- View/download PDF