1. The effects of building-related factors on classroom relative humidity among North Carolina schools participating in the ‘Free to Breathe, Free to Teach’ study
- Author
-
Marshall, S. W., Lipton, D. M., LoFrese, T., Richardson, D. B., Angelon-Gaetz, K. A., and Lamb, B.
- Subjects
education - Abstract
Both high and low indoor relative humidity (RH) directly impact indoor air quality (IAQ), an important school health concern. Prior school studies reported a high prevalence of mold, roaches, and water damage; however, few examined associations between modifiable classroom factors and RH, a quantitative indicator of dampness. We recorded RH longitudinally in 134 North Carolina classrooms (n= 9066 classroom-days) to quantify the relationships between modifiable classroom factors and average daily RH below, within, or above levels recommended to improve school IAQ (30–50% or 30–60% RH). The odds of having high RH (>60%) were 5.8 (95% Confidence Interval (CI): 2.9, 11.3) times higher in classrooms with annual compared to quarterly heating, ventilating, and air conditioning (HVAC) system maintenance, and 2.5 (95% CI: 1.5, 4.2) times higher in classrooms with HVAC economizers compared to those without economizers. Classrooms with direct expansion split systems compared to chilled water systems had 2.7 (95% CI: 1.7, 4.4) times higher odds of low RH (60%) of those without setbacks. This research suggests actionable decision points for school design and maintenance to prevent high or low classroom RH.
- Published
- 2015
- Full Text
- View/download PDF